Pacific Institute research on data center water usage found that a single facility can withdraw from a daily average of 270 gallons to 3.9 million gallons. For a typical facility, 74% of the water withdrawn is consumed. Google’s 2025 location table lists its Council Bluffs, IA campus at 1,746.4 million gallons withdrawn. Microsoft’s total water withdrawal reached 13,266 megaliters (ML) in FY25, up from 6,794 ML in FY20.
Withdrawal, discharge and consumption are three different measures, and each source reports its own. Campus figures for Google and Microsoft follow, then water sources, efficiency, water stress, AI prompts and state planning. National totals sit with the data center energy and water figures.
Key Takeaways
- Across 65 data centers, the Pacific Institute found a median withdrawal of 44.3 million gallons a year against an average of 159 million gallons.
- A typical facility consumed 74% of the water it withdrew, while the overall average was 59%.
- Google’s Council Bluffs, IA campus withdrew about 39 times the Pacific Institute’s median facility.
- Microsoft consumed 8,170 ML of the 13,266 ML it withdrew in FY25, about 62%.
- 13% of Google’s 2025 freshwater withdrawal came from sources at high risk of water depletion or scarcity.
- Only 17% of data centers responded to the Texas Water Development Board, out of 341 surveys sent this year.
Editor’s Choice
- Google Council Bluffs withdrawal: 1,746.4 million gallons in 2025.
- Microsoft Quincy withdrawal: 1,292 ML in FY25.
- Google data center withdrawal: 13,562 million gallons in 2025, with 3,039 million discharged.
- AWS water use effectiveness: 0.12 liters of water withdrawn per kilowatt-hour of IT load.
- Water per Gemini prompt: 0.26 milliliters for the median Gemini Apps text prompt.
- Peak vs average demand: peak daily water demand of 3 to 30 times the average.
Data Center Water Usage per Facility
- Across 65 data centers, water withdrawals ranged from 100,000 gallons to 1.4 billion gallons per year, or 270 gallons to 3.9 million gallons per day.
- Withdrawals for a typical facility, as represented by the median, were 44.3 million gallons per year (121,000 gallons per day).
- The average was much higher at 159 million gallons per year (436,000 gallons per day) because a small number of facilities withdrew exceptionally large volumes.
- The average facility withdrew about 3.6 times the median.
- Peak daily water demand at data centers can range from 3 to 30 times the average, against hospital peaking factors typically below 3.
| Measure | Average | Median | Minimum | Maximum | Sample size |
|---|---|---|---|---|---|
| Annual withdrawal (million gallons) | 159 | 44.3 | 0.10 | 1,410 | 65 |
| Annual consumption (million gallons) | 123 | 32.1 | 0.01 | 1,010 | 65 |
| Annual discharge (million gallons) | 56.1 | 22.6 | 0.10 | 400 | 36 |
| Estimated daily withdrawal (million gallons) | 0.436 | 0.121 | 0.00 | 3.86 | 65 |
| Consumptive ratio (unitless) | 0.59 | 0.74 | 0.10 | 0.94 | 36 |
Source: Pacific Institute, 2026
About This Data
- Compiled from 15 source documents: 8 company reports and pages from Google, Microsoft, Amazon and Meta, 2 federal publications, 4 research publications and 1 advocacy testimony.
- Publication dates run from December 2024 to September 2026.
- Paid market-research reports were excluded, and units stay as each source reports them.
- Figures are reviewed on a rolling basis and updated when sources publish new editions.
How much water do data centers use?
A typical data center withdrew 44.3 million gallons of water a year, about 121,000 gallons a day, across the 65 facilities in the Pacific Institute’s study. The average was 159 million gallons because a small number of facilities withdrew exceptionally large volumes.
Google Data Center Withdrawal at Selected Campuses
- Google’s Council Bluffs, IA campus withdrew 1,746.4 million gallons in 2025, discharged 400.4 million and consumed an estimated 1,346.0 million.
- Council Bluffs withdrew about 39 times the Pacific Institute’s median facility of 44.3 million gallons.
- Council Bluffs, Mayes County and New Albany together held about 31% of Google’s data center withdrawal.
- Douglas County, GA drew 394.3 million gallons of its 440.6 million from reclaimed wastewater.
- Midlothian, TX withdrew 263.6 million gallons and Red Oak, TX 67.0 million, while Phoenix, AZ withdrew 0.5 million gallons.
- Ashburn, VA withdrew 76.5 million gallons, and Bristow, VA withdrew 359.6 million.
View the data
Which Google data center uses the most water?
Of the Google campuses in the table above, Council Bluffs, IA withdrew the most water. Council Bluffs, IA withdrew 1,746.4 million gallons, against 1,396.7 million at Mayes County, OK and 1,008.1 million at New Albany, OH. Google reports these figures by location, and the hyperscale data center statistics show how many such campuses now operate.
Recent Developments
- September 30, 2026: Amazon and Microsoft announced a water replenishment project in Hesse, Germany, expected to return more than 750 million liters of water annually to the local groundwater supply once completed.
- September 2026: An issue brief from the Pacific Institute found withdrawals ranging from 100,000 gallons to 1.4 billion gallons per year across 65 data centers.
- September 1, 2026: Public Citizen’s testimony said that of the 341 surveys the Texas Water Development Board sent this year, only 17% of the data centers responded.
- August 31, 2026: HARC put current New Mexico data centers at 502 Mgal/yr of total water use, and planned sites at 16 Bgal/yr.
- July 2026: AWS reported a water use effectiveness of 0.12 for 2025, a 20% drop year over year.
Google Water Withdrawal by Year
- Google’s global operational water withdrawal rose from 6,297 million gallons in 2021 to 14,689 million gallons in 2025.
- The 2025 total was about 2.3 times the 2021 level.
- Data centers accounted for about 92% of Google’s 2025 withdrawal.
- Offices and other facilities withdrew 1,127 million gallons in 2025 and discharged 781 million.
- Company-wide discharge rose from 1,735 million gallons in 2021 to 3,820 million in 2025.
View the data
Microsoft Datacenter Withdrawal by Site
- Microsoft’s Quincy (WA) datacenter withdrew 1,292 ML in FY25 and used 1,381,569 MWh of electricity.
- Phoenix (AZ) withdrew 981 ML and recorded 2,675 ML of water replenishment.
- Phoenix’s replenishment was about 2.7 times its FY25 withdrawal.
- Atlanta (GA) withdrew 19 ML, and Manassas (VA) 11 ML.
- The figures cover Microsoft-owned datacenters for the fiscal year ended June 30, 2025.
View the data
By the numbers: Microsoft’s Quincy (WA) datacenter withdrew 1,292 ML in FY25, Phoenix (AZ) 981 ML and San Antonio (TX) 420 ML. Boydton (VA) withdrew 362 ML and Des Moines (IA) 264 ML, and the table covers Microsoft-owned datacenters for the fiscal year ended June 30, 2025.
Phoenix’s water ledger belongs to the wider record of data centers in Arizona, while Boydton and Ashburn sit inside the data centers in Virginia cluster.
Microsoft Water Withdrawal by Region
- North America accounted for 7,366 ML of Microsoft’s 13,266 ML total water withdrawal in FY25.
- That is about 56% of the company total.
- Withdrawal in Asia rose from 1,306 ML in FY20 to 4,082 ML in FY25.
- Asia’s FY25 withdrawal was about 3.1 times its FY20 level.
- Third-party sources supplied 8,162 ML of the 8,170 ML Microsoft consumed in FY25.
- These regional totals cover Microsoft’s whole operation, offices included, so they are not datacenter-only figures.
View the data
Data Center Water Withdrawal vs Consumption
- Microsoft’s total water consumption rose from 3,990 ML in FY20 to 8,170 ML in FY25, while discharge rose from 2,804 ML to 5,096 ML.
- Microsoft consumed about 62% of the water it withdrew in FY25.
- Microsoft’s FY25 total withdrawal was about 1.95 times its FY20 level.
- Google’s data centers discharged 3,039 million gallons in 2025, about 22% of what they withdrew.
View the data
Key finding: Pacific Institute data show that a typical facility consumed 74% of the water withdrawn, while the overall average for the data centers was considerably lower at 59%, a ratio reported for 36 facilities rather than the 65 behind the volume averages. The lower mean reflects a subset of facilities likely using air or once-through cooling systems that consume less of the water withdrawn.
What is the difference between water withdrawal and water consumption?
Withdrawal is all the water a facility takes in, and consumption is the part that does not go back. For a typical facility, 74% of the water withdrawn is consumed and unavailable for other uses within the water basin. Microsoft withdrew 13,266 ML in FY25, consumed 8,170 ML and discharged 5,096 ML.
Where Data Center Water Comes From
- Potable water made up 10,949 million gallons of the 13,562 million gallons Google’s data centers withdrew in 2025.
- That is about 81% potable water.
- Of the estimated 11 billion gallons withdrawn by the facilities the Pacific Institute evaluated, 76% was potable water and 24% came from non-potable sources, including recycled water and seawater.
- AWS already uses recycled water for cooling at 24 data centers and will expand water recycling to more than 120 locations in US states and counties by 2030.
View the data
Do data centers use drinking water?
Municipal drinking water systems were the primary water source for the data centers the Pacific Institute studied, and 76% of the water withdrawn was potable. At Google, about 81% of data center withdrawal was potable water. Douglas County, GA ran mostly on reclaimed wastewater, at 394.3 million gallons of 440.6 million.
Data Center Water Use Effectiveness (WUE) by Company
- AWS reported a water use effectiveness (WUE) of 0.12 L/kWh in 2025, down from 0.25 L/kWh in 2021 and 20% lower year over year.
- AWS measures WUE as liters of water withdrawn per kilowatt-hour of IT load (L/kWh).
- Amazon says its 0.12 L/kWh is 7 times better than the industry average, which it puts at a withdrawal WUE of 0.84 L/kWh calculated from a consumption WUE of 0.56 L/kWh.
- AWS’s WUE fell about 52% from 2021 to 2025.
- Lawrence Berkeley National Laboratory notes that some hyperscale facilities report WUE values of 0.1-0.3 L/kWh for similar systems.
- The aggregate median WUE for the hyperscale category in Lawrence Berkeley National Laboratory’s model is 0.32, or 0.40 if one cooling system had a median WUE of 0.2 L/kWh.
View the data
A WUE figure only compares with another on the same basis, and each of the largest data center companies that publishes one states its own.
What is a good WUE for a data center?
No single benchmark applies, because WUE is reported on different bases. AWS reports 0.12 L/kWh on a withdrawal basis, while the aggregate median WUE for hyperscale sites in Lawrence Berkeley National Laboratory’s model is 0.32, or 0.40 under an alternative cooling assumption of 0.2 L/kWh.
Data Centers in Water-Stressed Basins
- 13% of Google’s 2025 freshwater withdrawal came from sources at high risk of water depletion or scarcity, while 72% came from sources at low risk.
- Google assigns each data center a low, medium or high water scarcity level by applying its data center Water Risk Framework.
- Meta’s target is to restore 200% of the water it consumes in high water stress regions and 100% in medium water stress regions.
- Meta’s operational restoration projects returned over 1.59 billion gallons of water in 2024.
- AWS was 75% of the way toward its water positive goal in 2025, up from 53% in 2024.
- Lawrence Berkeley National Laboratory puts the average water intensity factor for electricity use in the US overall at 4.35 L/kWh.
View the data
Worth noting: Microsoft’s Phoenix (AZ) datacenter withdrew 981 ML in FY25 and recorded 2,675 ML of water replenishment. Amazon counts a NABU wetland project in Hesse, Germany, toward its goal to return more water to communities than it uses in its data center direct operations by 2030. Replenishment need not happen in the basin the water came from.
AI Water Footprint per Prompt and Model
- Google estimates the median Gemini Apps text prompt uses 0.24 watt-hours of energy and consumes 0.26 milliliters of water, or about five drops.
- A preprint from the University of California, Riverside and UT Arlington estimates that training the GPT-3 language model in Microsoft’s US data centers can directly evaporate 700,000 liters of clean freshwater.
- GAO found that companies are generally not reporting details of generative AI’s energy and water use, and that estimates of water consumption by generative AI are limited.
- In December 2024, Microsoft said its zero-water-for-cooling datacenter design would avoid the need for more than 125 million liters of water per year per datacenter.
| Estimate | Value | Estimated by |
|---|---|---|
| Water per median Gemini Apps text prompt, comprehensive method | 0.26 mL | |
| Water per median Gemini text prompt, active TPU and GPU only | 0.12 mL | |
| Direct evaporation, GPT-3 training in Microsoft US data centers | 700,000 liters | University of California, Riverside and UT Arlington (preprint) |
| Global AI water withdrawal, 2027 projection | 4.2 to 6.6 billion cubic meters | University of California, Riverside and UT Arlington (preprint) |
| Water avoided per datacenter per year, zero-water cooling design | more than 125 million liters | Microsoft |
Source: Google Cloud 2025, University of California, Riverside 2025, Microsoft 2024
Training runs belong to the wider machine learning statistics on model compute, and the AI data center build-out adds the campuses where that water is drawn.
How much water does an AI prompt use?
Google estimates a median Gemini text prompt consumes 0.26 mL of water under its comprehensive methodology and 0.12 mL when only active TPU and GPU consumption is counted. The gap comes from what each method counts, so a per-prompt figure needs its method attached before it is compared with another company’s.
State Planning for Data Center Demand
- HARC puts New Mexico data centers at 0.05% of current water use today and planned sites at 1.6% of total water use.
- Planned sites would use about 32 times as much water as New Mexico’s current data centers.
- HARC puts average direct cooling water use at 95 gal/MWh.
- Public Citizen’s testimony says only one-third of data centers surveyed in 2024 responded to the Texas Water Development Board.
- Only 17% of the data centers responded to the 341 surveys the Texas Water Development Board sent this year, according to Public Citizen’s testimony.
- HARC estimates that direct and indirect water consumption for existing data centers in Texas totaled as much as 25 billion gallons in 2025.
- A mid-size data center can use up to 300,000 gallons per day for cooling, while a large or hyperscale facility can use up to 5 million gallons per day, according to Public Citizen’s testimony.
| New Mexico data center water (Mgal = million gallons, Bgal = billion gallons) | Current | Planned sites |
|---|---|---|
| Direct cooling | ~152 Mgal/yr | ~6.3 Bgal/yr |
| Indirect (power plant cooling) | 350 Mgal/yr | 9.7 Bgal/yr |
| Total | 502 Mgal/yr | 16 Bgal/yr |
Source: HARC, August 2026
The TWDB five-year plan does not account for individual data center water use in its water plan. That gap leaves planners for the data centers in Texas working from partial returns.
Conclusion
A typical facility consumes 74% of the water it withdraws, and the Pacific Institute’s median facility withdrew 44.3 million gallons a year. Google’s Council Bluffs, IA campus withdrew 1,746.4 million gallons, and Microsoft’s Quincy (WA) datacenter withdrew 1,292 ML. Read beside the broader data center statistics, that spread explains why per-site disclosure says more than a national average.
Planned New Mexico data centers would use 16 Bgal/yr, against 502 Mgal/yr today. New sites in the data center construction pipeline will decide how much of that planned figure arrives, and facility-level reporting will matter more to water planners than any new national average.